dlms
A DLMS/COSEM client and server for smart meters in pure Go, with the COSEM interface classes, HDLC, the wrapper, IEC 62056-21, DLMS over NB-IoT and LoRaWAN, OBIS and India's IS 15959 catalogue.

The client associates with no, low or high-level security (mechanisms 2
to 7, security suites 0 to 2, every ciphering form, general signing,
third-party protection, V.44 compression), reads, writes and acts with
block transfer, reads profiles by range, opens pushes, reaches meters
behind data concentrators, and keeps invocation counters across
restarts, with logical or short name referencing and the ACCESS service.
The server package is the meter side: associations with the same
mechanisms and suites, GET, SET, ACTION, ACCESS and the short name
services with block transfer and general block transfer, and pushes,
serving the typed COSEM objects of package classes (40 interface
classes), with general ciphering, signing, third-party layers and
compression on the meter side too. Around them: a data concentrator in
gateway and logical-device mode, the IEC 62056-21 meter side with its
mode E hand-over, an IS 15959 meter builder, and the LoRaWAN and NB-IoT
meter end. Below them are the IEC 62056-46 HDLC data link, the IEC 62056-42
physical layer with Hayes modems, the IEC 62056-4-7 wrapper over TCP and
UDP, the gateway prefix, and a LoRaWAN bridge with SCHC. The A-XDR and
xDLMS APDU encodings come from
gosem (MIT); security,
transports and everything above are this module's. No cgo. It was written
for SigmaM2M, a oneM2M platform, where it serves its DLMS/COSEM, IEC
62056-21 and M-Bus integrations, and has no dependency on it.
Features
| Area |
Implemented |
Not implemented |
| Client (IEC 62056-5-3:2023, Green Book) |
Logical name referencing, with or without the ciphering application context (applicationContext: automatic, ln, ln-ciphering, sn or sn-ciphering); short name referencing (referencing: sn: read, write, parameterized access, data blocks, methods, base names from the association SN object list, HLS through the association SN object); the ACCESS service (Client.Access, in general-glo or general-ded ciphering when protected); raw exchanges on an association (Association.Exchange); image transfer as a state machine (Client.TransferImage: resume, resend of missing blocks, verify, activate, status polling); mechanisms 0 to 7; suites 0, 1 and 2; authentication, encryption or both; global and dedicated keys; service-specific, general-glo, general-ded and general ciphering (identified, wrapped, one-pass and static agreed keys); general signing; the broadcast key and unconfirmed broadcast associations; third-party protection; V.44 compression; ciphered release; replay checks; key transfer and agreement, key pairs and certificates of class 64; key rotation as a state machine (KeyRotation: keys stored wrapped before they are sent, checked by a new association, rolled back or resumed after a crash); pushes (data-notification, general-glo, general block transfer, HDLC; encryption-only pushes only on opt-in); data concentrators in gateway and logical-device mode; profile reading by range; identity check; a crypto policy hook at association time |
Mechanism 2 is the common AES-ECB reading and is manufacturer specific (confirm per make); short name writes in data blocks |
Server (IEC 62056-5-3:2023, package server) |
Associations per client address: no security, low-level, HLS mechanisms 2 to 7; suites 0, 1 and 2; authenticated, encrypted or both; global and dedicated keys; service-specific, general-glo, general-ded and general ciphering (identified, wrapped, one-pass and static agreed keys, answered under a fresh key of the request's kind); general signing (required per association or answered when used); V.44 compression; third-party layers (signing and agreed-key ciphering, answers signed, ciphered or unprotected for the third party); the broadcast key; invocation counter checks and a counter object; ciphered release; unconfirmed associations. GET, SET and ACTION normal, with list and in data blocks both ways; ACCESS; short name read, write and unconfirmed write with parameterized access and data blocks; general block transfer; access rights per association; the current association LN or SN object with its object list; data-notification pushes (plain or general-glo) to TCP, UDP or HDLC links and from a push setup object; the wrapper over TCP and UDP and HDLC; in-process sessions (NewSession) for other carriers |
Pushes in general ciphering or signed; key transfer and agreement methods of the security setup object act on classes.SecuritySetup only when the application wires them |
Data concentrator (package concentrator) |
Gateway mode (annex C prefix, by network ID and physical address) and logical-device mode (by server SAP) on one head-end connection; meters in the process, over HDLC, the wrapper, NB-IoT or any gosem transport; sessions per meter and client running side by side; pushes forwarded on open connections or to the head end's listener |
The IEC 62056-8-20 mesh and vendor-specific concentrator protocols (DC-specific objects, meter lists by the DC's own commands) |
IEC 62056-21 meter (package iec6205621/meter) |
Modes A to E, programming mode (P1, R1 to R6, W1 to W5, E2, B0, B1), partial blocks, annex C formatted codes, annex B wake-ups, mode D pushes, several meters on one line, mode E hand-over to a server.Server; fault switches for test benches |
Rate changes on a real serial port (over a converter the converter's rate holds) |
IS 15959 meter (package is15959/meter) |
Every Part 1, 2 and 3 profile as a server.Server: objects, profiles that agree with the registers, event logs, push setups, associations with keys and rights, disconnect control events, the billing script, image transfer |
Values are made up (no metrology); pushes are the application's (server.Push) |
LoRaWAN and NB-IoT meter (package lpwan/enddevice) |
The device end of SCHC on a LoRaWAN radio (ACK-on-Error uplinks, ACK-Always downlinks, class A polling, pushes) and an NB-IoT meter in power saving mode (wake with a push, active time), serving a server.Server or any handler |
Radio drivers are the application's (Radio); the DLMS UA LoRaWAN profile is not public, so its choices are settings |
COSEM objects (IEC 62056-6-2:2023, package classes) |
40 interface classes as data (attributes, methods, short name offsets); typed Go objects for data, registers (3, 4, 5), register activation, profile generic (capture, by range, by entry, FIFO), clock, script table, schedule, special days, associations LN and SN (object lists encoded and parsed), SAP assignment, image transfer (initiate, blocks, verify, activate), IEC local port, activity calendar, register monitor, single action schedule, IEC HDLC setup, push setup, TCP-UDP and IPv4 setup, security setup, disconnect control, limiter; Generic for the others |
Account (111), charge (113), M-Bus slave port setup (25); push setup versions above 0; profile sort methods other than FIFO |
| HDLC (IEC 62056-46, ISO/IEC 13239) |
Frame format type 3; 1-, 2- and 4-octet addresses; SNRM/UA negotiation (information fields up to 2030, windows up to 7); segmentation both ways; RR polling; RNR; FRMR; DM; UI frames, sent segmented on request (SegmentUI; IEC 62056-46 forbids them, so off by default); modulo 128 numbering with SNRME and windows up to 127 for ISO/IEC 13239 peers (Modulo, with fallback to modulo 8); the inactivity time-out; multi-drop lines on one connection |
Modulo 128 on the multi-drop Bus and the line helpers; modulo 128 is checked against our own station only |
| Physical layer (IEC 62056-42) |
PH services over a TCP connection to a converter; Hayes dialling, answering, escape and hang-up; the identification service |
Collisions of several meters calling at once |
| Wrapper (IEC 62056-4-7, 62056-9-7) |
Header checks; whole WPDUs from TCP however they are split; one WPDU per UDP datagram; reserved wPorts |
|
| Gateway (IEC 62056-5-3 annex C) |
E6/E7 prefix with network ID and physical address |
Vendor concentrator variants; the IEC 62056-8-20 mesh |
| NB-IoT and LoRaWAN |
UDP from behind carrier NAT with reply windows, sleeping meters, a command queue; SCHC over LoRaWAN (RFC 8724, RFC 9011) with settable FPorts, rules and header; regional limits |
The DLMS UA LoRaWAN profile is not public: its choices are settings; network servers are the application's (NetworkServer) |
| IEC 62056-21 |
Modes A to E, programming mode, annex C formatted codes, annex B wake-ups, mode D, the mode E hand-over to HDLC; 7E1 emulated through converters |
Baud rates above 19200 |
| OBIS (IEC 62056-6-1:2023, EN 13757-1:2021) |
Value groups A to F with every range, abstract, electricity and media 4 to 9 codes, the COSEM objects of 62056-6-2 with their classes, reduced ID codes, point names that never collide |
Names for manufacturer, utility and country specific codes (they keep their code) |
| IS 15959 (India) |
Parts 1 (categories A, B, C), 2 (single- and three-phase, with Amendments 1 and 2) and 3 (CT and CT/PT): objects, rights per association, profiles, events, ESW bits, push setups, associations, commands; an IS 16444 event classification; the special days table in Parts 2 and 3 (our reading: no IS 15959 table lists it) |
|
Choosing a DLMS/COSEM library
Compared from each project's source at the versions named, in October
2026; "tested" means our interop tests ran it (see below). Cells marked
"not checked" were not verified in the source. Check the projects
themselves before relying on a row.
|
this module |
gosem v1.3.5 (Go) |
Gurux.DLMS.Java (gurux.dlms 4.0.95) |
Gurux.DLMS.Python (gurux-dlms 1.0.203) |
| Licence |
Apache-2.0 |
MIT |
GPL-2.0 or a commercial licence |
GPL-2.0 or a commercial licence |
| Client / server |
both (client tested against Gurux's server, server against Gurux's client) |
client |
both (tested as a server) |
both (tested as a client) |
| Data concentrator, IEC 62056-21 meter, LoRaWAN/NB-IoT meter end |
yes (the concentrator tested with Gurux's client through it) |
no |
gateway prefix as a client; no concentrator |
gateway prefix as a client (tested); no concentrator |
| Server-side general ciphering with key agreement, signing, third party, compression |
yes (checked with this module's client only, whose side dlms-sim's separately written meter checks) |
no |
not checked |
not checked |
| Referencing |
logical and short name (both tested against Gurux) |
logical name |
logical and short name (tested) |
logical and short name (tested) |
| ACCESS service |
yes, client and server (client tested against Gurux's server and vectors) |
no |
yes (tested as a server; its server answers gets only, acknowledging sets and actions without doing them) |
not checked |
| General block transfer |
server; client for pushes |
no |
not checked |
fails in its own code when receiving (tested) |
| Typed object model |
40 classes as data, 25 as Go types |
no |
yes, all classes |
yes, all classes |
| Transports |
HDLC (with modems and multi-drop), wrapper over TCP and UDP, serial ports, IEC 62056-21 mode E, the gateway prefix, NB-IoT and LoRaWAN with SCHC |
HDLC, wrapper, TCP, serial port |
HDLC and wrapper (tested); others not checked |
HDLC and wrapper (tested); others not checked |
| Low-level security, HLS mechanism 2 |
yes (tested both ways) |
low-level only: no HLS passes 3 and 4 in its client |
yes (tested) |
yes (tested) |
| HLS-GMAC (mechanism 5), suite 0 ciphering |
yes (tested both ways) |
ciphering of suite 0 APDUs; no GMAC pass 3 and 4 |
yes (tested) |
yes (tested) |
| Mechanisms 3, 4, 6, 7; suites 1 and 2; general ciphering and signing; third party; compression |
yes (suite 1 with mechanism 6, general-glo and dedicated keys tested against Gurux's server; suites 0 to 2 in general-glo, general-ded and service-specific ciphering tested against Gurux's client) |
no |
suite 1, general-glo (tested) |
suites 0 to 2, general-glo and general-ded (tested) |
| Block transfer, profile by range |
yes (tested both ways) |
yes |
yes (tested) |
yes (tested) |
| Pushes, data concentrators, invocation counters kept across restarts |
yes (pushes sent and received) |
data notifications received |
not checked |
not checked |
| OBIS model and IS 15959 catalogue |
yes |
no |
no IS 15959 catalogue |
no IS 15959 catalogue |
| cgo / runtime |
none, pure Go |
none, pure Go |
JVM |
Python |
This module builds on gosem for the A-XDR and xDLMS APDU encodings and
adds everything above them. Pick it for a Go head end that must talk to
Indian (IS 15959) or other secured meters over HDLC, TCP, UDP, NB-IoT or
LoRaWAN, or for a Go meter, gateway or test bench that must answer as a
meter, data concentrator or test bench that must answer as one (IS 15959
meters built from the catalogue, IEC 62056-21 optical ports, LoRaWAN and
NB-IoT meters), without a JVM or a GPL dependency. Pick Gurux when you
need every interface class modelled as a typed object, or the most widely
deployed implementation with commercial support; pick gosem alone for
unsecured or low-level-security reads where a small dependency matters
most.
Install
go get github.com/cB-Sigma/dlms@latest
Requires Go 1.25 or later.
Quick start
import (
gdlms "gitlab.com/circutor-library/gosem/pkg/dlms"
"github.com/cB-Sigma/dlms/cosem"
"github.com/cB-Sigma/dlms/wrapper"
)
sec := cosem.SecurityConfig{Name: "M1", Authentication: "hls-gmac", Security: "authenticated-encrypted",
BlockCipherKey: "...", AuthenticationKey: "...", DedicatedKey: true}
hls, _, err := sec.Build()
r := &cosem.ICReservation{Store: myStore, Name: "M1"} // an iotsec.Store: counters survive a restart
c := cosem.NewClient(cosem.ClientConfig{
Transport: func(client int) (gdlms.Transport, error) {
return wrapper.New("tcp", "192.0.2.10:4059", client, 1, 10*time.Second)
},
ClientAddress: 48,
HLS: hls,
InvocationCounter: &cosem.FrameCounterObject{OBIS: "0.0.43.1.3.255"},
Reserve: func(ic uint32, first bool) (uint32, error) { return r.Reserve(ctx, ic, first) },
})
err = c.Connect()
v, err := c.Get(3, "1.0.32.7.0.255", 2) // voltage L1
The examples in the documentation that run and check their output are
cosem.ExampleProtect (the Green Book's suite 0 example),
cosem.ExampleICReservation, obis.ExampleDescribe,
is15959.ExampleGet, hdlc.ExampleFrame, wrapper.ExampleEncode,
gateway.ExampleEncode, phy.ExampleIdentifyRequest,
iec6205621.ExamplePointName and lpwan.ExampleLookupRegion.
cosem.ExampleClient and iec6205621.ExampleOpenSession need a meter,
so they compile but do not run here; dlms-sim
runs the same steps against its simulated meters.
A meter:
import (
"github.com/cB-Sigma/dlms/classes"
"github.com/cB-Sigma/dlms/server"
)
s := &server.Server{SystemTitle: []byte("SGM00001")}
s.Add(&classes.Clock{LN: "0.0.1.0.0.255"},
&classes.Register{LN: "1.0.32.7.0.255", Value: axdr.CreateAxdrLongUnsigned(23050), Scaler: -2, Unit: 35})
s.Associations = []*server.Association{
{ClientAddress: 16},
{ClientAddress: 48, Mechanism: 5, Policy: cosem.SecAuthentication | cosem.SecEncryption, Key: key, AuthKey: ak},
}
addr, err := s.ListenWrapper(":4059")
Documentation
API reference: https://pkg.go.dev/github.com/cB-Sigma/dlms
| Package |
What it does |
cosem |
The client: SecurityConfig (settings as text) and Associate/Client (AARQ/AARE, HLS mechanisms 2 to 7, the frame counter read through the public client); SecureTransport (suites 0 to 2, every ciphering form, general signing, the broadcast key, third-party layers, compression, ciphered release); ICReservation, Counter and PushCounter over an iotsec.Store; SecuritySetup (class 64); pushes (OpenProtectedPush, MapPush, ServeHDLCPushes, general block transfer); InboundConn (meter-initiated connections); Gateway (data concentrators); profile reading by range; NewPortClient over a port another protocol opened; serial lines with the IEC 62056-21 mode E opening; DLMS APDUs inside M-Bus (Seal, Open, Request, Exchange) |
server |
The meter side: Server with Associations per client address (general ciphering keys, signing, compression, third parties), Add objects, ListenWrapper, ListenUDP, ListenHDLC, ServeWrapper, ServeHDLC, NewSession; Push, PushTo, PushHDLC; Stats |
concentrator |
A data concentrator: Concentrator with Meters (gateway mode) and Logical devices, Listen, Serve, Forward, ForwardTo; Downstream devices: Local, LogicalDevice, Transport |
iec6205621/meter |
The IEC 62056-21 meter side: Meter (Listen, ListenOn, Serve), Line for several meters on one port, ModeE |
is15959/meter |
An IS 15959 meter: New (a server.Server for a profile), Options, Associations; Populate, Recapture, RaiseEvent, Row over a Store |
lpwan/enddevice |
The LoRaWAN (LoRaWAN, Radio, MemRadio) and NB-IoT (NBIoT) meter end, serving a Handler (ServerHandler) |
classes |
The interface classes: Lookup/All (attributes, methods, short name offsets), the Object interface, typed objects (Register, Clock, ProfileGeneric, DisconnectControl, ImageTransfer, ...), Generic, object list encoding and parsing, COSEM date-times |
hdlc |
Frames, SNRM/UA negotiation, a client transport for gosem (Client), a server Station, a multi-drop Bus, a frame Scanner |
phy |
The physical layer over any net.Conn: PH services, Hayes modem procedures, the identification service, a simulated modem |
wrapper |
The wrapper header and a gosem transport over TCP or UDP |
gateway |
The gateway prefix for meters behind a data concentrator |
lpwan |
DLMS over NB-IoT (UDP reply windows, sleeping meters, a command queue) and LoRaWAN (a SCHC bridge to a NetworkServer, an in-memory MemNS), each meter as a net.Conn of wrapper frames |
iec6205621 |
IEC 62056-21 sessions over serial ports or converters, programming mode, annex C, wake-ups, mode D, mode E; reduced-ID point names |
obis |
OBIS codes: parse (full, short and reduced forms), validate, ranges, what a standard code means with its classes, camel-case point names (1.0.21.7.0.255 is activePowerImportL1) |
is15959 |
IS 15959 Parts 1 to 3 as data under one point name per OBIS code; EventInfo |
Testing
go test -race ./...
The tests use the worked examples of the standards (the IEC 62056-46
FCS table and frames, the IEC 62056-4-7 annex A.4 split, the IEC
62056-5-3:2023 Table 30 and annex E ciphering and release examples, the
Green Book's suite 0 example), RFC 3394 key wrap and NIST CAVS ECDSA
vectors, and fuzzing of the ciphered and general APDU decoders and of
IEC 62056-21 messages. Tests carry
// Covers: SIG-... comments: requirement IDs of the SigmaM2M project's
compliance report, which mean nothing else here.
The client's tests against a simulated meter (every mechanism, suite and
ciphering form, third-party layers, compression, data concentrators, the
LoRaWAN bridge, IEC 62056-21 sessions) are in
dlms-sim, so this module does not
depend on its simulator.
Interop tested against
Against Gurux, written independently of this module, on 2026-10-11
(interop/, a nested test-only module that starts the peer in Docker;
cd interop && SIGMA_DLMS_INTEROP=1 go test -v ./...). Peer: the
server example of Gurux.DLMS.Java at commit 709c3a0 (gurux.dlms 4.0.95
from Maven Central), built in maven:3.9.9-eclipse-temurin-17: its
logical name servers (HDLC and wrapper) and its short name servers (HDLC
and wrapper); and Gurux's Python client against our server. The
server's own tests (server/) drive it with this module's client over
the wrapper on TCP and UDP and HDLC, every mechanism and suite included.
| Check (our client against the Gurux server) |
Wrapper |
HDLC |
| No security, public client: logical device name, invocation counter |
pass |
pass |
| Low-level security: clock, register with scaler and unit, data object |
pass |
pass |
| Low-level security with a wrong password: refused, reported as such |
pass |
|
| HLS mechanism 2 (Gurux's AES reading of it) |
pass |
|
| HLS mechanism 2 with authenticated and encrypted APDUs (suite 0) |
pass |
|
| HLS-GMAC, suite 0, authenticated and encrypted APDUs: clock, register, profile generic by range, the whole 10 002-row buffer in 942 blocks |
pass |
|
HLS-GMAC with Gurux's default settings (no ciphering context, plain APDUs): our automatic context is refused with diagnostic 2; applicationContext: "ln" associates and reads clock, register and profile by range |
|
pass |
| Profile generic: the whole buffer (10 002 rows, 858 blocks) and by range |
pass |
pass |
| ACCESS: three gets in one request, with HLS mechanism 2 and with HLS-GMAC and authenticated and encrypted APDUs (ACCESS then in general-glo ciphering) |
pass |
|
| Security suite 1 (HLS-SHA256, authenticated and encrypted APDUs) |
pass |
|
| General-glo ciphering (general protection proposed) |
pass |
|
| A dedicated key: the association (HLS passes 3 and 4 under the global key) |
pass |
|
| Short name referencing against the Gurux short name server: object list, logical device name, clock, register, profile columns and the whole 10 002-row buffer in 847 data blocks, low-level security and HLS mechanism 2 |
pass |
pass |
Check (Gurux's client, gurux-dlms 1.0.203 for Python in python:3.12.10-slim, against our server) |
Wrapper |
HDLC |
| No security, low-level, HLS mechanism 2, HLS-GMAC with authenticated and encrypted APDUs: clock, register, scaler and unit, a data object |
pass |
pass |
| Profile generic whole (in data blocks), by entry and by range; a 1 500-octet SET in data blocks; an ACTION |
pass |
pass |
| HLS-GMAC in security suites 0, 1 and 2, each in general-glo, general-ded, service-specific, and service-specific with a dedicated key ciphering (the server counted every form) |
pass |
suite 1 |
| Short names: object list, reads, a write, the profile whole, by entry and by range, with low-level security and HLS mechanism 2 |
pass |
pass |
Through our concentrator (v0.3.0): gateway mode to a meter in the process and to one over HDLC, and logical-device mode; no security, low-level security (profile whole, by entry, by range) and HLS-GMAC with authenticated and encrypted APDUs |
pass |
|
An IS 15959 Part 2 three-phase meter built by is15959/meter (v0.3.0): public client, meter reader (low-level, encrypted APDUs), utility settings (HLS mechanism 2, authenticated and encrypted APDUs); nameplate, registers, block load profile whole, by entry and by range |
pass |
|
Gurux's published unit-test vectors (Gurux.DLMS.Android at commit
d3489a4, fetched at run time, not kept here): the AES-GCM
authentication, encryption and authenticated encryption of a GET request
match Protect and Unprotect, the AES key wrap vectors match WrapKey
and UnwrapKey, and our ACCESS request encoder gives the octets of its
accessRequestTest (two gets, two sets of activity calendar values)
while DecodeAccessResponse reads its accessResponseTest.
These runs found and fixed: our HLS mechanism 2 challenge is one AES
block long (the form both the ECB and Gurux's CBC reading accept); the
application context is selectable for meters that take HLS-GMAC only
without the ciphering context; with a dedicated key, HLS passes 3 and 4
now go under the global key, as Gurux's server and client expect (the
association is not established until pass 4); short name data blocks are
asked for by the number of the block received. The Gurux Python client
against dlms-sim's meter is in
dlms-sim.
Not checked against another implementation, and why: Gurux's Java server
example answers requests ciphered under a dedicated key with exception
1/2, so reads under a dedicated key are checked only against Gurux's
client (our server) and dlms-sim; gurux-dlms 1.0.203 for Python fails in
its own code on a ciphered short name reply_to_HLS_authentication, on
short name data blocks and on receiving general block transfer
(AttributeError), so those paths are checked with our own client; Gurux's
server acknowledges ACCESS sets and actions without doing them; suite 2,
general ciphering with key agreement, general signing, third-party
protection and compression on our client are checked against dlms-sim
only (Gurux's example server has no such association). The server side
of general ciphering with key agreement, general signing, third-party
layers and compression (v0.3.0) is checked with this module's client
only; the IEC 62056-21 meter is checked with this module's client and
SigmaM2M's adapter; the LoRaWAN and NB-IoT meter ends with package
lpwan's head-end bridge. Not yet: a real meter or data concentrator.
The v0.3.0 runs found that gurux-dlms 1.0.203 for Python, behind a
gateway, leaves the prefix off its ciphered APDUs and ciphers it with
the APDU; the concentrator and the server now accept that (see the
changelog).
- dlms-sim: simulated DLMS/COSEM
meters (also served by this module's
server), a data concentrator and
an IEC 62056-21 meter.
- mbus: wired and wireless M-Bus,
which carries DLMS APDUs with this module's
cosem.
- schc: SCHC and V.44, used for
LoRaWAN and compression.
- iotsec: the store and crypto
policy seams.
Status
v0.x: the API may change before v1.
Contributing
See CONTRIBUTING.md.
Security
See SECURITY.md to report a vulnerability privately.