mbus

Wired M-Bus, Wireless M-Bus and OMS in pure Go: a bus master, a telegram decoder with every security mode, data records with OBIS codes, and the M-Bus adaptation layer for LPWAN.

Go Reference test Go

The wired master follows the EN 13757-2:2018+A1:2023 link layer and the EN 13757-3:2025 procedures: frame count bits per address, repeats and answer timing, primary and secondary selection, the wildcard search with collision handling, multi-telegram reads, alarms, clock synchronisation, baud rate switching and image transfer. The wireless side decodes EN 13757-4 frames and the EN 13757-7:2025 and OMS security layers (ELL, AFL, TPL; security modes 2, 3, 5, 7 to 10 and 13; SITP; compact frames), reads iM871A and Amber receiver sticks, and schedules downlinks into meters' receive windows. One decoder of data records serves both, with the annex H translation to OBIS codes. No cgo. It was written for SigmaM2M, a oneM2M platform, where it serves its wired M-Bus, Wireless M-Bus, LoRaWAN and raw-payload integrations, and has no dependency on it.

Features

Area Implemented Not implemented
Wired link (EN 13757-2:2018+A1:2023) FT1.2 frames, ACK/NACK, SND_UD2, the frame count bit per address (A1 rules), three attempts, the answer window, an idle line after broadcasts, collisions in the search Repeater management (address 251) beyond addressing; the physical layer (a level converter does it)
Wired application (EN 13757-3:2025) Variable and fixed data, multi-telegram reads, alarms, application select and reset, set primary address (with a lost-ACK check), baud rate switching, clock synchronisation (types I, J, M), synchronize, application errors, image transfer (annex I), DLMS behind CI 60h/61h and 7Ch/7Dh, transport PDUs Manufacturer-specific procedures
Data records Every DIF/VIF of clause 6 and annex C, combinable VIFEs, LVAR, dates and times (types F, G, I, J, K, L, M), compact profiles (annex F), annex H OBIS codes, manufacturer codes, device types, TPL status flags Legacy Fahrenheit codes keep their code (no unit); manufacturer-specific payloads (no per-meter drivers)
Wireless link (EN 13757-4:2025) Formats A and B, CRCs, 3-out-of-6, mode F FEC, C fields, relayed (H) and repeated frames, duplicates The radio (a receiver stick does it); setting a stick's mode
Security (EN 13757-7:2025, OMS) Modes 2, 3 (DES, deprecated), 5, 7, 8, 9, 10, 13; ELL encryption; AFL MACs and fragments; KDF-A; counters and replay detection; SITP (annex A) both ways; OMS security profiles A to D (C: mode 13 TLS, annex F); sealing for meters and gateways Response-delay timing of downlinks (the D bit)
Receivers iM871A (HCI with CRC, RSSI, timestamp), Amber command mode, raw L framing, hex lines; a downlink Scheduler (one downlink per receive window, answers matched by access number) Other sticks' native protocols
MBAL (EN 13757-8) The control field and the LoRaWAN, UDP, CoAP/COSE/CBOR, MIOTY and Wize layouts Network handling (the caller's)
DLMS over M-Bus (EN 13757-1:2021) Transport PDUs (tpdu); with dlms's cosem, DLMS APDUs inside M-Bus

Choosing an M-Bus library

Compared from each project's source at the versions named, in October 2026. Cells marked "not checked" were not verified in the source. Check the projects themselves before relying on a row.

this module gombus v1.1.0 (Go) wmbusmeters 3.0.0 (C++) libmbus 0.10.3 (C)
Licence Apache-2.0 Apache-2.0 GPL-3.0-or-later BSD-3-Clause
What it is Go library Go library and a command a program (daemon and command line) with meter drivers C library and commands
Wired master: search, secondary addressing, multi-telegram reads yes, with collision handling, frame count bits per address, repeats yes (scan, secondary addressing, readdressing) not checked yes
Wired procedures: alarms, baud switch, clock sync, image transfer, application select and reset yes not checked not checked partial (not checked in detail)
Wireless decoding: formats A and B, CRCs yes, and 3-out-of-6 and mode F FEC yes yes no
Security modes 2, 3, 5, 7, 8, 9, 10, 13; ELL and AFL; SITP 0, 5, 7 (13 refused) 5, 7, ELL AES-CTR; others not checked none
Compact frames, OMS profiles A to D yes not checked compact frames yes; profiles not checked no
Receiver sticks iM871A, Amber, raw, hex; a downlink scheduler none (takes the telegram) many dongles, including iM871A, Amber and rtl-sdr serial and TCP for wired
Per-meter drivers (manufacturers' own payloads) no: standard data records only no over a hundred no
OBIS codes (EN 13757-3 annex H), MBAL (EN 13757-8) yes no no no
cgo / runtime none, pure Go none, pure Go a C++ program C (cgo from Go)

Pick this module for a Go gateway or head end that needs the security modes beyond 5 and 7, OMS profiles, receiver sticks, downlinks, OBIS codes or MBAL, without cgo. Pick wmbusmeters when the meters in front of you send manufacturer-specific payloads: it has drivers for over a hundred meters and decodes telegrams this module leaves undecoded (see the interop results below). Pick libmbus for wired M-Bus from C, and gombus for a small Go wired master with plain or mode 5 and 7 wireless decoding.

Install

go get github.com/cB-Sigma/mbus@latest

Requires Go 1.27.1 or later (tlsx, the TLS of security mode 13, needs it).

Quick start

import (
	"github.com/cB-Sigma/mbus/wired"
	"github.com/cB-Sigma/mbus/wireless"
)

// Wired: a converter on TCP (wired.OpenSerial for a local port).
conn, _ := net.Dial("tcp", "192.0.2.20:10001")
m := wired.NewMaster(2400)
m.SetPort(wired.NewPort(conn), 2400)
found, _ := m.Search(ctx)
a, _ := m.Select(ctx, wired.Target{Secondary: &found[0]})
m.ReadTelegrams(ctx, a, 8, func(t wired.Telegram) error {
	for _, r := range t.Records {
		fmt.Println(r.Name(), r.Value, r.Unit) // volume 12.345 m3
	}
	return nil
})

// Wireless: one telegram, with the meter's key.
tg, err := wireless.Decode(frame, wireless.FormatNoCRC, func(wireless.Header) []byte { return key })

The examples that run and check their output are wired.ExampleFrame_Encode, wireless.ExampleDecode, records.ExampleParseRecords, tpdu.ExampleSegmentAPDU and mbal.ExampleParseUDP. wired.ExampleMaster needs a bus, so it compiles but does not run here; mbus-sim runs the same steps against its simulated bus.

Documentation

API reference: https://pkg.go.dev/github.com/cB-Sigma/mbus

Package What it does
wired FT1.2 frames; Master (frame count bits, repeats, selection, SelectOne, the search, multi-telegram reads, REQ_UD1, application select and reset, set primary address, baud switch, clock synchronisation, image transfer); responses with variable or fixed data, application errors, DLMS APDUs; Port over a serial port (8E1) or a TCP converter
wireless Frame formats, CRCs, 3-out-of-6, FEC; Decode/Decoder (ELL, AFL, TPL, security modes, replay detection, SITP, compact frames with FormatCache); SealTPL, SealAFL, EncodeDownlink; Reader for iM871A, Amber, raw and hex receivers; Scheduler; TLS endpoints of mode 13
records Data records, names and UCUM units, compact profiles, OBIS codes (annex H), manufacturer codes, device types, status flags
tpdu DLMS/COSEM transport PDUs over M-Bus (EN 13757-1:2021 8.2.4)
mbal The MBAL control field and the LoRaWAN, UDP, CoAP/COSE/CBOR, MIOTY and Wize layouts (EN 13757-8)

Testing

go test -race ./...

The tests use the worked examples of the standards (EN 13757-3:2025 annexes F and G), every example frame of OMS Specification Volume 2 annex N with its keys, the example telegrams of the M-Bus documentation, four heat meter answers from libmbus's test suite (BSD-3-Clause, see NOTICE), RFC 3610, 4493 and 5649 vectors, and fuzzing of the wired frame, record and MBAL decoders. Tests carry // Covers: SIG-... comments: requirement IDs of the SigmaM2M project's compliance report, which mean nothing else here.

The master's tests against a simulated bus are in mbus-sim, so this module does not depend on its simulator.

Interop tested against

Against the published test data of two independent implementations, on 2026-10-11 (interop/, a nested test-only module that fetches the data at run time and keeps none of it here; cd interop && SIGMA_MBUS_INTEROP=1 go test -v ./...).

Peer and data Result
libmbus 0.10.3 (commit d617bd2), every frame of test/test-frames, compared record by record with libmbus's normalised XML 76 of 76 frames decoded; headers 75 equal, 1 different (M field 0000h printed as 0000, libmbus prints @@@); records 942 compared, 906 equal, 36 different, every difference explained: 21 manufacturer-specific VIFs whose data we keep raw where libmbus decodes the base VIF, 9 values coded invalid (we mark them, libmbus prints the digits), 4 combinable VIFEs (limit-exceed durations) that we apply and libmbus ignores, 1 "every year" date, 1 VIF with no defined meaning
wmbusmeters 3.0.0 (commit ac4f295), the telegrams of its driver tests and simulation files with the keys they give, compared with the JSON wmbusmeters prints 403 frames (364 wireless, 39 wired); 340 decoded. Meter ID 327 equal, 0 different; medium 323 equal, 0 different; values 540 compared, 484 equal, 1 different (explained), 55 where the driver reads a field that is not a plain record at storage 0. Not decoded, all explained: 48 proprietary payloads that wmbusmeters' drivers cut up by byte position, 4 manufacturer-specific CI fields, 3 Diehl group telegrams in the manufacturer's own security scheme, 4 encrypted with no key in the test, 2 compact frames whose format is not given (or whose rebuilt frame fails the full-frame CRC wmbusmeters does not check), 1 DES telegram without the meter ID our check requires, 1 broken on purpose

These runs found and fixed two decoder bugs: the order of a plain-text VIF's text and its combinable VIFEs as Elvaco meters send them, and the byte order of the extended link layer's payload CRC. wmbusmeters decoding the telegrams of our simulated meter is recorded in mbus-sim. Also tested: the worked examples of the standards and OMS (above).

Not yet: a real meter, receiver stick or master on a live bus; per-meter drivers for manufacturers' own payloads (the 48 proprietary and 3 Diehl telegrams above), planned for v0.2.0.

  • mbus-sim: a simulated wired M-Bus segment, wireless meters and receiver sticks.
  • dlms: DLMS/COSEM, whose OBIS model the records use and whose client carries DLMS inside M-Bus.
  • iotcrypto: AES-CCM for security mode 10 and COSE.
  • tlsx: the TLS of security mode 13.

Status

v0.x: the API may change before v1.

Contributing

See CONTRIBUTING.md.

Security

See SECURITY.md to report a vulnerability privately.

Licence

Apache-2.0 (see LICENSE and NOTICE). Copyright 2026 Abhinav Gautam.

Directories

Path Synopsis
Package mbal is the M-Bus adaptation layer (MBAL) of EN 13757-8:2023: the one-byte MBAL control field (optionally introduced by the CI field CFh) that carries M-Bus upper layers (AFL, TPL, APL of EN 13757-7 and -3) over LPWAN technologies, and the per-technology payload layouts of the annexes: LoRaWAN (FPort is the control field, Annex D.6), NB-IoT/LTE-M over UDP or CoAP/COSE/CBOR (Annex C.4), MIOTY (Annex E.5) and Wize (Annex F.4).
Package mbal is the M-Bus adaptation layer (MBAL) of EN 13757-8:2023: the one-byte MBAL control field (optionally introduced by the CI field CFh) that carries M-Bus upper layers (AFL, TPL, APL of EN 13757-7 and -3) over LPWAN technologies, and the per-technology payload layouts of the annexes: LoRaWAN (FPort is the control field, Annex D.6), NB-IoT/LTE-M over UDP or CoAP/COSE/CBOR (Annex C.4), MIOTY (Annex E.5) and Wize (Annex F.4).
Package records decodes the M-Bus application layer that wired and wireless M-Bus share (EN 13757-3:2025): data records with their DIF, DIFEs, VIF and VIFEs (clause 6 and annexes A to C and E), the compact profiles of annex F, the OBIS codes of annex H (on .../libs/dlms/obis), manufacturer codes, device types and the TPL status byte.
Package records decodes the M-Bus application layer that wired and wireless M-Bus share (EN 13757-3:2025): data records with their DIF, DIFEs, VIF and VIFEs (clause 6 and annexes A to C and E), the compact profiles of annex F, the OBIS codes of annex H (on .../libs/dlms/obis), manufacturer codes, device types and the TPL status byte.
Package tpdu is the transport sub-layer that carries DLMS/COSEM APDUs over wired and wireless M-Bus (EN 13757-1:2021 8.2.4): an APDU split into transport PDUs with a fragment counter and FIN, and joined again.
Package tpdu is the transport sub-layer that carries DLMS/COSEM APDUs over wired and wireless M-Bus (EN 13757-1:2021 8.2.4): an APDU split into transport PDUs with a fragment counter and FIN, and joined again.
Package wired is wired M-Bus: the EN 13757-2:2018+A1:2023 link layer (FT1.2 frames, ACK and NACK, the frame count bit per address, repeats, answer timing, collisions) and the EN 13757-3:2025 application procedures of a master: primary and secondary addressing (a command to a meter named with wildcards goes only to one selected meter), the secondary address search, multi-telegram reads, class 1 data and alarms, application select and reset, set primary address, baud rate switch, clock synchronisation and image transfer (annex I); plus the fixed data structure, application errors and DLMS/COSEM responses.
Package wired is wired M-Bus: the EN 13757-2:2018+A1:2023 link layer (FT1.2 frames, ACK and NACK, the frame count bit per address, repeats, answer timing, collisions) and the EN 13757-3:2025 application procedures of a master: primary and secondary addressing (a command to a meter named with wildcards goes only to one selected meter), the secondary address search, multi-telegram reads, class 1 data and alarms, application select and reset, set primary address, baud rate switch, clock synchronisation and image transfer (annex I); plus the fixed data structure, application errors and DLMS/COSEM responses.
Package wireless is Wireless M-Bus and OMS: the EN 13757-4 link layer (frame formats A and B with their CRCs, the 3-out-of-6 code, C fields, radio modes, FEC of mode F), the EN 13757-7:2025 transport and security layers (ELL, AFL with fragmentation, TPL short and long headers, security modes 5 and 7 to 10 and the deprecated DES modes 2 and 3, KDF-A, message counters with replay detection, mode 13 TLS records), security information transfer (SITP, annex A), compact frames (EN 13757-3:2025 annex G), the OMS Volume 2 profiles, the framings of receiver sticks (iM871A, Amber, raw, hexadecimal lines), and frames a gateway sends to bidirectional meters with a scheduler that sends one frame per receive window (Scheduler).
Package wireless is Wireless M-Bus and OMS: the EN 13757-4 link layer (frame formats A and B with their CRCs, the 3-out-of-6 code, C fields, radio modes, FEC of mode F), the EN 13757-7:2025 transport and security layers (ELL, AFL with fragmentation, TPL short and long headers, security modes 5 and 7 to 10 and the deprecated DES modes 2 and 3, KDF-A, message counters with replay detection, mode 13 TLS records), security information transfer (SITP, annex A), compact frames (EN 13757-3:2025 annex G), the OMS Volume 2 profiles, the framings of receiver sticks (iM871A, Amber, raw, hexadecimal lines), and frames a gateway sends to bidirectional meters with a scheduler that sends one frame per receive window (Scheduler).