nautilus
SCADA, built like software. A Go + SvelteKit toolkit for building
industrial control and supervisory systems the way software engineers already
work — version control, tests, CI/CD, code review — instead of inside a
proprietary vendor IDE.
Write your control logic in IEC 61131-3 — Structured Text, Ladder, or
Function Block, the portable standard languages — or in native Go. Host it
on a deterministic scan loop. Build the operator screens on the included
SvelteKit component kit. Bring your own field I/O, redundancy and historian
through small, documented interfaces. Develop it in VS Code. Ship it like
any other binary.
For teams that want the libraries and the seams, not a walled garden.
Why
A PLC program should be code: diffable, reviewable, unit-tested, built by CI,
rolled back with one command, and observable from your editor. Vendor tooling
makes almost none of that possible. nautilus makes control logic a first-class
software artifact and keeps the runtime a tiny, pure-stdlib core you can read.
Architecture
runtime/ scan loop · tag bus · program host (compile, hot-swap, retained state)
lang/st IEC 61131-3 Structured Text: lexer, parser, lowering
lang/fbd Function Block Diagram: netlist text ⇄ diagram model, transpiles to ST
lang/ld Ladder Diagram: rung text ⇄ ladder model, transpiles to FBD
lang/ir typed IR + tree-walking virtual machine (pure stdlib)
io/ Driver seam — bring your own bus (Modbus, EtherNet/IP, OPC-UA, sim)
eip/ EtherNet/IP driver for Allen-Bradley Logix: pure-Go CIP stack,
tag browse + UDT import codegen, polling io.Driver, Logix emulator
server/ tag API over HTTP: JSON snapshot, SSE stream, tag writes
cmd/nautilus the developer CLI: `new` (scaffold) · `check` (CI compile) · `lsp`
hmi/ SvelteKit digital-twin component kit + realtime SSE client
tools/vscode-iec/ VS Code extension: syntax, diagnostics, go-to-def, live values
examples/heated-tank/ a complete controller built on the libraries
The public API is the seams. You implement interfaces to bring your world:
| Interface |
You provide |
io.Driver |
your field bus (Modbus / EtherNet-IP / OPC-UA / REST rack / sim) |
retain.Store |
where retained memory persists — file and k8s ConfigMap ship in retain/ |
runtime.Coordinator |
redundancy / leader election — a k8s Lease elector ships in leader/ |
hist.Sink |
where process history is archived — Postgres + nautilus historian ship in hist/ |
Getting started
Prerequisites: Go 1.24+ with $(go env GOPATH)/bin on your PATH, and
VS Code for the editor experience.
1. Install the CLI
go install github.com/joyautomation/nautilus/cmd/nautilus@latest
This gives you nautilus new (scaffold a project), nautilus check
(headless Structured Text compile for CI), and nautilus lsp (the language
server the VS Code extension uses).
2. Scaffold a project
nautilus new my-plant # the tour: 3 tasks, 3 IEC languages, simulated plant
nautilus new my-plant --template minimal # one task, one program, one test
nautilus new my-plant --template sdk # Go project, for a custom field bus
nautilus new my-plant --template sdk-demo # Go project with plant physics in Go
A nautilus project is your logic and a manifest. Run, test, and ship it
with the CLI alone — no toolchain:
cd my-plant
nautilus run # scan loop + dashboard + tag API on http://localhost:8080
nautilus test # acceptance tests, in virtual time
nautilus build # emit ./my-plant — a self-contained controller binary
nautilus.yaml declares the tasks (one program file each, any language,
own scan rates), the tags by role, the server, and the field driver
(loopback for bring-up, EtherNet/IP by configuration). nautilus build
appends the project to the runner and emits one deployable binary — no Go
toolchain anywhere.
Your logic gets real tests. *_test.yaml files run against a virtual
clock, so a ten-second on-delay or a PI loop's settling time is asserted
exactly, deterministically, in milliseconds — the assertions a wall clock
makes impossible:
- name: low-temp alarm waits its full 10 s
suspend: [sim] # freeze the plant; drive the value directly
given: { TempC: 45.0 }
steps:
- advance: 9.5s
expect: { TempLowAlm: false } # the TON has not elapsed
- advance: 1s
expect: { TempLowAlm: true } # ... and now it has
The fixture is nautilus.yaml itself — tasks, rates, roles, seeds — so a
retuned gain can't drift away from what the tests verify. Assertions are
tag matchers or ST expressions (ABS(TempC - TempSP) < 0.5) compiled by
the same compiler as your logic.
Go is the SDK, not the base: --template sdk when you need a custom
field bus or richer simulation physics. Same runtime, with the manifest
written as code.
Run it bare for the interactive form, sv-create style — pick the template,
the program language, and the features (CI workflow, VS Code setup, git
init). An sdk template also asks for a module path, and gives you
main.go, program.st, a driver.go seam to fill in, Go acceptance
tests, CI, and .vscode/ recommendations.
3. Run and test it
cd my-plant
nautilus test # the acceptance suite, in virtual time
nautilus run # scan loop + tag API on http://localhost:8080
An sdk project is an ordinary Go program — go mod tidy, go run .,
go test ./... — and its Go tests get the same virtual clock through the
acceptance package.
Open http://localhost:8080 for the built-in live dashboard, or
GET /api/state for the raw tag snapshot. Setpoints are click-to-set right
in the tag table (BOOLs get a toggle); inputs and outputs are not editable,
because the driver rewrites one before every scan and the logic rewrites the
other after. Reads are open; set NAUTILUS_TOKEN=<secret> to require a token
on writes.
4. Develop in VS Code
Install nautilus IEC 61131-3 from the
VS Code Marketplace
or Open VSX. It
currently ships on the pre-release channel, so use Install Pre-Release
Version (or code --install-extension joyauto.vscode-iec --pre-release).
Open your project folder — it recommends the extension — and with go run .
running you get compile diagnostics as you type, go-to-definition / hover /
completion, and live tag values as pills next to identifiers in
program.st.
5. Make it yours
- Write control logic in
program.st (IEC 61131-3 Structured Text).
- Swap
plant.go for a real io.Driver — Modbus, EtherNet/IP, OPC-UA, your
bus — when you have hardware. The control logic doesn't change.
- Add an HMI:
npm install @joyautomation/nautilus-hmi in a SvelteKit app for
SCADA faceplates and an SSE realtime client.
- Ship it like any Go binary:
go build, deploy. The scaffolded CI gates on
go test and nautilus check.
Under the scaffold, a complete controller — an IEC program on a 10 Hz scan
loop driving a field device — is about 30 lines:
rt, _ := runtime.New(runtime.Options{
Program: program, // IEC 61131-3 Structured Text (go:embed)
Driver: NewPlant(), // anything implementing io.Driver
Scan: 100 * time.Millisecond,
DtTag: "ScanDtS",
Tags: []runtime.TagDef{ // each tag's role, seed, and HMI docs — once
runtime.Input("LevelPct", runtime.Unit("%")),
runtime.Input("TempC", runtime.Unit("°C")),
runtime.Setpoint("TempSP", 65.0, runtime.Unit("°C")),
runtime.Setpoint("Kp", 12.0),
runtime.Setpoint("Ki", 0.15),
runtime.Output("PumpRun", runtime.Init(false)), // logic reads it back
runtime.Output("Heater", runtime.Unit("%")),
},
})
go rt.Run(ctx) // read inputs → run program → write outputs, every scan
How tags work — where they come from, which role fits which job, and the
one rule that bites (reads fault, writes create) — is spelled out in
The tag model below.
Or, from a clone of this repo, run the worked example:
go run ./examples/heated-tank
nautilus · heated-tank — Ctrl+C to stop
level 60.0% temp 60.0°C pump off heater 61% scans 9
level 59.9% temp 60.4°C pump off heater 63% scans 20
...
The control logic itself lives in examples/heated-tank/program.st —
pump hysteresis and a PI temperature loop, in plain Structured Text.
Talking to a real PLC (EtherNet/IP)
Point the importer at an Allen-Bradley Logix controller and it generates the
types and bindings your project needs — committed source, not runtime config:
nautilus eip browse --host 192.168.1.10 # see what's on the controller
nautilus eip import --host 192.168.1.10 \
--tags 'Line1*,Program:MainProgram.*' \
--writable 'Line1Cmd*'
That writes eip_types.st (a TYPE block mirroring the controller's UDTs plus
suggested VAR_EXTERNAL declarations) and eip_manifest.go (the tag manifest).
Wire it into main.go:
driver, err := eip.New("192.168.1.10", EIPManifest,
eip.WithSlot(0),
// Polling policy is configuration, not codegen: re-running the import
// refreshes the tag catalog without touching these.
eip.WithScanRate(500*time.Millisecond), // default scan class
eip.WithScanClass("fast", 100*time.Millisecond),
eip.WithScanClass("slow", 10*time.Second),
eip.WithTagClass("fast", "Line1_PIT_*"), // globs on tag/device names
eip.WithTagClass("slow", "*_Totals"),
eip.WithTagClass(eip.NoPoll, "Line1Cmd*"), // cataloged + writable, never polled
)
driver.Start(ctx)
rt, err := runtime.New(runtime.Options{
Program: program,
Driver: driver,
Inputs: driver.InputNames(),
Outputs: driver.OutputNames(),
})
The driver polls each scan class on its own interval over one connection
(UDTs arrive as real struct values in ST), validates the manifest against
the live controller at startup so type drift fails loudly, and writes
changed outputs back on change — the runtime behaves like a PLC peer on the
network. Pure Go, no cgo; tested against an in-repo ControlLogix emulator
(eip/logixserver).
Online edits — change logic while it runs
nautilus has two planes. The cold plane — connections, the tag manifest,
scan classes, server wiring — is Go, and changes ship through CI/CD as a new
binary. The hot plane — the ST program and tag values — can change live,
the way you online-edit a traditional PLC. Because the program is data on a
VM, a warm swap carries retained state (PID integrals, timers, counters)
across by name and type; a failed compile leaves the running program
untouched, so a typo can never fault the controller.
Enable it per controller (off by default — pushing logic is code execution
on a control system):
srv := server.New(rt, server.Options{OnlineEdits: true})
Then from VS Code: Download Program to Controller warm-swaps your open
program, Diff Program with Controller shows running-vs-workspace, and a
status-bar indicator flags when the controller runs something other than the
committed file. Edits are ephemeral by design — a restart reverts to the
program the binary embeds, so committing the ST to git is the only way an
edit becomes permanent. The rule of thumb falls out of the two planes:
logic you want to tune online, write in ST; infrastructure, write in Go.
Pulling a field edit back to git closes the loop. Pull Program from
Controller (VS Code) or nautilus pull --host <controller> writes the
running program back into your program file — the inverse of download — so
you review it with git diff and commit. Only the program file is rewritten;
generated type files are never touched. nautilus pull --check reports drift
and exits non-zero, so CI can fail a build when a controller has un-pulled
edits. Composition is a single definition shared by the runtime, the language
server, download, and pull, so a program round-trips losslessly.
Working against a remote controller. All of this — live values, online
edits, pull — works over the network, not just against a local process. A
scaffolded controller binds loopback by default; set NAUTILUS_ADDR=0.0.0.0:8080
to expose the tag API to other machines, and point the editor at it with the
nautilus.runtimeUrl setting (nautilus pull takes --host). Exposing the
API on the network also exposes its write surface, so set NAUTILUS_TOKEN on
the controller and the matching nautilus.token in the editor — reads and
nautilus pull stay open, but tag writes and online edits then require the
token.
Publishing to MQTT (Sparkplug B)
Expose a controller's tags to a Sparkplug host (Ignition, any Sparkplug-aware
SCADA) with the sparkplug package. The runtime is the edge node; each
io.Driver becomes a device whose birth/death follows its link:
node, _ := sparkplug.New(rt, sparkplug.Config{
BrokerURL: "tcp://broker:1883", GroupID: "Plant", EdgeNode: "Line1",
BdSeqFile: "/var/lib/nautilus/line1.bdseq",
},
// Publish classes are report-by-exception groups, like scan classes:
sparkplug.WithDefaultRBE(sparkplug.RBE{Deadband: 0.5, MaxInterval: 30 * time.Second}),
sparkplug.WithPublishClass("fast", sparkplug.RBE{Deadband: 0.1, MaxInterval: 5 * time.Second}),
sparkplug.WithMetricClass("fast", "PIT_*"),
// The EtherNet/IP driver's tags become a device; DBIRTH/DDEATH track its health.
sparkplug.WithDevice(sparkplug.Device{
ID: "plc1", Tags: driver.InputNames(),
Health: func() bool { return driver.Health().Connected },
}),
)
node.Start(ctx)
Types map faithfully (BOOL→Boolean, integer→Int64, REAL→Double, UDT→Template),
a SCADA host can write tags back via NCMD, and Node Control/Rebirth is
honored. The node passes the Sparkplug TCK edge-node profile — CI runs the
joyautomation/sparkplug-tck-go harness against a live node on every push. MQTT
and protobuf live only in this package; the runtime core stays stdlib-only.
Three languages, one program model
A program file is .st, .fbd, or .ld — pick per task, mix freely in
one controller. The graphical languages are text first: an .fbd is a
netlist, an .ld is rung text, both diff/review/merge like code, and the
VS Code extension projects them into a full graphical editor (right-click
→ "Open With → FBD Diagram" / "Ladder Diagram") where every gesture is a
structural edit to the text underneath.
(* interlocks.ld *)
PROGRAM Interlocks
VAR_EXTERNAL
TempC : REAL; HiTempAlm : BOOL; HornAck : BOOL; Horn : BOOL;
END_VAR
LD
RUNG hitemp (* comparison as a contact, with a 5 s on-delay *)
GT(TempC, 90.0) t2:TON(PT := T#5S) ( HiTempAlm )
RUNG horn (* the alarm sounds the horn until the operator acks *)
HiTempAlm /HornAck ( Horn )
END_LD
END_PROGRAM
Rung grammar: series = AND, [ a | b ] = OR (nests), /x = NC contact,
( x ) / ( S x ) / ( R x ) coils, FN(args) as a contact (must yield
BOOL), inst:TYPE(args) puts a timer/counter in the rung with power
driving its standard pin, and ET => Var captures block outputs. Each
language transpiles one hop (ld → fbd → st) into the same IR, so
functions, user FUNCTION_BLOCKs, arrays, diagnostics, live values, online
edits, and visual diffs work identically everywhere. nautilus new --language ld (or fbd) scaffolds a project in that language. The full
reference — evaluation semantics and every built-in — is
docs/functions.md.
The tag model
The tag store is the seam everything meets at: the IEC program, the field
driver, the HMI/API, and the editor's live values all read and write the
same named values. One scan looks like this:
driver.ReadInputs() ──(Input tags)──▶ ┌───────────┐ ──(Output tags)──▶ driver.WriteOutputs()
│ tag store │
HMI / POST /api/tags ──(writes)─────▶ │ │ ──(reads)────────▶ HMI / editor pills
└───────────┘
▲ │
program writes │ program reads
(coils) ▼
A VAR_EXTERNAL declaration is a binding, not a creation. Declaring
TempC : REAL; in your program tells the compiler "resolve this name in
the tag store at scan time" — it does not make the tag exist. Existence
comes from a write, and there are exactly four writers:
- a seed in the Go composition (initial value, exists from scan one),
- a driver delivering it as an input each scan,
- an operator writing it through the HMI or
POST /api/tags,
- the program itself assigning it (a coil write creates the tag).
The one rule that bites: writes create, reads fault. Reading a tag
nobody has ever written stops the scan with undefined tag <name> —
deliberately, so a mis-wired binding fails loudly instead of running on a
silent zero. The classic trap is a seal-in latch that reads its own coil
on scan one, before the first write; the fix is a seed. (In the FBD
diagram, with live values on, externals with no backing tag are flagged —
an amber no tag badge in the vars panel and on any chip that reads one —
so you see this before the download, not after.)
Declaring tags: one entry per tag
runtime.Options.Tags states each tag's role once — which direction it
moves each scan, its initial value, and its HMI documentation — instead of
spreading the name across the flat Inputs/Outputs/Seed/Meta fields
(all of which still work and compose with Tags):
Tags: []runtime.TagDef{
// Field input: the driver produces it. NOT seeded — if the driver
// doesn't deliver it, you want the loud fault, not a silent zero.
// (The name must also appear in the driver's ReadInputs map.)
runtime.Input("TempC", runtime.Desc("Tank temperature"), runtime.Unit("°C")),
// Operator setpoint / config: seeded so it exists from scan one;
// the HMI or POST /api/tags writes it later.
runtime.Setpoint("TempSP", 65.0, runtime.Unit("°C")),
// Field output: the logic produces it, the driver consumes it.
// Init() any output the logic also READS — the seal-in latch.
runtime.Output("PumpRun", runtime.Init(false), runtime.Desc("Pump run command")),
// Logic-owned state that must survive read-before-write: latches,
// integrators, mode words.
runtime.State("Mode", int64(0), runtime.Desc("0=off 1=auto 2=manual")),
},
Picking a role, by use case:
| You want a tag that… |
Use |
Backed by |
| comes from a sensor / the field |
Input(name, …) |
driver ReadInputs map + this entry |
| goes to an actuator / the field |
Output(name, …) |
your logic writes it (coil) |
| …and your logic also reads it (latch) |
Output(name, Init(v), …) |
the seed covers scan one, then the coil |
| an operator adjusts (setpoint, gain, limit) |
Setpoint(name, initial, …) |
the seed, then HMI / POST /api/tags |
| your logic owns across scans (integrator) |
State(name, initial, …) |
the seed, then the coil |
| the HMI watches but the field never sees |
plain coil write — no entry |
the program creates it on first write |
Adding a new field input end to end is three lines in three places, all
by the same name: declare it in the program (VAR_EXTERNAL testExt : REAL;
— or from the diagram's vars panel), produce it in the driver
("testExt": p.testExt in the ReadInputs map), and bind it in the
composition (runtime.Input("testExt")). The Inputs list is a deliberate
allowlist — a driver can't spray arbitrary names into the store — which is
why the middle step alone isn't enough.
Structuring logic: functions and function blocks
When a program outgrows one file, IEC 61131-3's unit of reuse is the
FUNCTION_BLOCK (stateful — each instance keeps its own timers,
integrals, latches) and the FUNCTION (stateless). nautilus sticks to
the standard here on purpose: there is no vendor-style "call another
program" — a program is a scheduling unit, a function block is a reuse
unit, and reaching for reuse means writing a block.
Blocks live in library files — .st files holding only TYPE,
FUNCTION, and FUNCTION_BLOCK declarations — and compose ahead of the
program:
//go:embed blocks.st
var blocks string
rt, _ := runtime.New(runtime.Options{
Program: program, // .st or .fbd
Libraries: []string{blocks}, // TYPEs, FUNCTIONs, FUNCTION_BLOCKs
...
})
(* blocks.st *)
FUNCTION_BLOCK PI
VAR_INPUT SP : REAL; PV : REAL; KP : REAL; KI : REAL; DT : REAL; END_VAR
VAR_OUTPUT OUT : REAL; END_VAR
VAR integral : REAL; err : REAL; END_VAR
err := SP - PV;
integral := LIMIT(0.0, integral + KI * err * DT, 100.0);
OUT := LIMIT(0.0, KP * err + integral, 100.0);
END_FUNCTION_BLOCK
(* program.st — one instance per control loop *)
VAR tic : PI; END_VAR
tic(SP := TempSP, PV := TempC, KP := Kp, KI := Ki, DT := ScanDtS);
Heater := tic.OUT;
The pieces that make this first-class rather than a convention:
- Callable from any IEC language. The same
PI block instantiates
from an FBD diagram (tic : PI(SP := TempSP, ...)) exactly like a
built-in TON — author blocks once, use them from whichever language
fits the logic. (Authoring blocks in FBD/LD is on the roadmap;
today libraries are ST.)
- The tooling composes the same way. The VS Code extension, the LSP,
nautilus check, and nautilus pull all treat sibling library files
as in-scope for the program, byte-identically to Libraries — so
online edits round-trip losslessly and CI sees what the runtime sees.
- Instance state is retained. A block's
VAR section persists
across scans, and PLC-style online edits carry it across program swaps
by name and type — a PI keeps its integral through a live logic
change, like a real controller.
nautilus new scaffolds this shape: the PI controller ships in
blocks.st, instantiated from program.st.
More than one program: tasks
The spec's answer to "many programs" isn't calling between them — it's the
resource/task model: several programs scheduled at their own rates
against one shared tag store. Options.Tasks is exactly that:
rt, _ := runtime.New(runtime.Options{
Program: fastLogic, // the MAIN task: owns field I/O
Scan: 10 * time.Millisecond,
Tasks: []runtime.Task{
{Name: "temperature", Program: pidLoops, Scan: 250 * time.Millisecond, DtTag: "PidDtS"},
{Name: "totals", Program: totalizers, Scan: time.Second, DtTag: "TotDtS"},
},
})
Scans never overlap — tasks serialize on one lock, so every scan sees a
consistent tag snapshot. The main task reads inputs and writes outputs;
additional tasks compute against the store at their own pace, each with
its own measured-dt tag and its own health in Stats().Tasks (rendered
in the built-in dashboard and the HMI kit's ScanDiagnostics).
Every program online-edits, both directions. Programs are addressed by
POU name — PROGRAM <Name> is a program's identity. GET /api/program
lists the resource's programs; a PUT routes automatically by the POU name
in the submitted source, and ?pou= / ?task= select one explicitly for
GET/rollback. In VS Code that means a workspace with one program file per
task Just Works: open the file, Download/Diff/Rollback target that task's
program, retained state carries across the swap. And nautilus pull
reconciles the whole resource: every controller program pulls back into
the workspace file declaring its POU (a new program lands in
<POU>.st/.fbd), so a field edit to any task is reviewable and
committable — --check fails CI on drift in any of them.
The full language reference — how a scan evaluates each language, ladder
power-flow semantics, and every built-in operator, function, and function
block with signatures and behavior — is in
docs/functions.md.
Status
Early. This is the extracted, generalized core of a working demo
(mini-scada). What's here now:
- ✅
lang/st + lang/ir — the Structured Text VM (pure stdlib, tested)
- ✅
lang/stgen — build ST type declarations functionally in Go and render
them to source (stgen.Struct("Motor", stgen.Field("Speed", stgen.REAL), …)),
for generating UDTs from a schema; validates output by compiling it. This is
the codegen path — the compiler stays the single source of truth
- ✅
runtime — scan loop, tag bus, program host + hot-swap, and PLC-style
online edits: warm-swap the ST program while it runs, carrying retained
state (PID integrals, timers, counters) across by name and type, with
one-step rollback
- ✅
io — the Driver seam + an in-memory driver
- ✅
sparkplug — MQTT Sparkplug B edge node: publishes the tag store to a
broker (the runtime is the edge node; each io.Driver is a device whose
DBIRTH/DDEATH tracks its connection health), faithful datatypes, UDTs as
templates, NCMD writeback, and publish classes with report-by-exception
(deadband + min/max interval), mirroring scan classes. Passes the
joyautomation/sparkplug-tck-go edge-node conformance profile in CI
- ✅
eip — EtherNet/IP driver for ControlLogix/CompactLogix: pure-Go (no
cgo) CIP client with connected messaging and batched reads, tag-list + UDT
template upload, nautilus eip import codegen (ST TYPE block + Go tag
manifest), write-on-change outputs, and a Logix controller emulator
(eip/logixserver) for hermetic integration tests
- ✅
server — tag API: JSON snapshot, SSE stream, tag writes (HMI + editor),
and a gated program API for online edits (GET/PUT /api/program, rollback)
- ✅
tools/vscode-iec/ online edits — Download Program to Controller, diff
running-vs-workspace, rollback, and a sync-status indicator
- ✅
cmd/nautilus — CLI: interactive project scaffold, headless ST compile
check for CI, and the ST language server
- ✅
tools/vscode-iec/ — VS Code extension: syntax, compile diagnostics,
go-to-definition, hover, completion, inline live tag values
- ✅
examples/heated-tank — a runnable controller serving the tag API
- ✅
examples/heated-tank-nogo — the same plant as a manifest project:
four tasks in three IEC languages (physics simulated in ST), zero Go,
nautilus run / nautilus build
- ✅
examples/hmi-demo — a SvelteKit operator screen on the HMI kit:
tank faceplate, trends, setpoint write-back, driver-connection cards,
and scan diagnostics from one SSE stream
- ✅
hmi/ — @joyautomation/nautilus-hmi
on npm: Svelte 5 SCADA faceplates (Tank, Gauge, Trend, Pump, Valve…), app
primitives, a generic SSE realtime client, and a themeable token layer
- ✅
lang/sfc — Sequential Function Chart: steps, transitions, and actions
on the same IR, with LSP support, a graphical VS Code editor, and a batch
example (examples/tank-batch-sfc)
Roadmap
- Retained-memory, redundancy, and historian packages behind clean interfaces
- An HMI starter in
nautilus new
- Native-Go function blocks alongside ST (both lowering to the same IR)
- FUNCTION_BLOCKs authored in FBD/LD (today: ST)
- Vendor-format import (Studio 5000 L5X, TIA, PLCopen XML) → nautilus
- A test harness for acceptance tests that gate deploys (from mini-scada)
License